MTP 5637 Clamp-On Ground Resistance Tester

Part Number:
MTP 5637
In Stock?
Stock may be available
please call (877)766-5412 to confirm

Quantity

Price:
$1571.43 USD (change)

 

The MTP 5637 advances the usability of clamp-on ground testing.
The larger jaw opening allows tests on a wider variety of ground rods and installations. Auto-Detects if jaw is open or if there is ground noise.

Comes complete in hard sided carry case and calibration loop is included.

Othe features include:

  • Non-Contact Ground Resistance Measurement
  • No Auxiliary Electrode Needed
  • Jaw Diameter 35 mm
  • Jaw Opening 38 mm
  • Range 0.025 – 1500 Ohm
  • 116 Sets of Memory
  • Programmable Hi and Lo Alarm
  • Programmable Data Logging
  • CAT II 600V, CAT III 300V, EN 61010-2-032
The Good:


The Bad:


The Bottom Line:

Full Review

Applications:
  • Measure electrical ground rod and grid resistance
  • Use on multi-grounded systems without disconnecting the ground rod under test
  • Measure resistance and continuity of grounding loops around pads and buildings
  • Measure leakage current flowing to ground or circulating in ground systems
  • Conduct field surveys and retrieve and analyze readings at a later time
  • Use on cell towers and telecommunication sites
  • Use on pools, spas and other consumer installations
  • Non-Contact Ground Resistance Measurement
Features:
  • No Auxiliary Electrode Needed
  • 0.025 - 1500 Ohms measurement range
  • Ground Wire O 23mm/0.9 inch¯
  • Leakage Current (0.200mA - 10.00mA)
  • Hi-Lo Alarm (Go - No Go)
  • Memory of 116 records
  • Programmable Data Logging
  • Auto Detect of Jaw Open and Ground Noise
  • Compliant with Safety Standard EN61010-2
  • CAT II 600V , CAT III 300V
General Specifications:

Jaw Opening: 38mm (1.49 inch¯)
Power Source: 9V Battery
Power Consumption: 40mA
Operating Temperature: 0°C to 40°C
Operating Humidity: Less than 80% RH
Dimensions: 258mm(L) x 100mm(W) x 47mm(H)
10.2¯(L) x 4¯(W) x 1.9¯(H)
Weight: 640g (1.4lbs)

Electrical Specifications:

Ground Resistance (Autorange):
Range
  • 0.025 ~ 0.250 Ohm
  • 0.250 ~ 9.999 Ohm
  • 10.00 ~ 99.99 Ohm
  • 100.0 ~ 199.9 Ohm
  • 200.0 ~ 400.0 Ohm
  • 400.0 ~ 600.0 Ohm
  • 600.0 ~ 1500.0 Ohm

Resolution
  • 0.002 Ohm
  • 0.02 Ohm
  • 0.04 Ohm
  • 0.4 Ohm
  • 2 Ohm
  • 5 Ohm
  • 20 Ohm

Accuracy of reading1
  • 1.5% 0.05 Ohm
  • 1.5% 0.1 Ohm
  • 2.0% 0.3 Ohm
  • 3.0% 1.0 Ohm
  • 5.0%5 Ohm
  • 10% 10 Ohm
  • 20% (Approx.)

1 Loop resistance noninductive, external field < 50A/m, external electrical field < 1V/m, conductor centered.

2 Resistance Measurement Frequency: 1.667KHz

Continuity

Beep if resistance < 40.00Ohm (Approximately)

Ground / Leakage Current (Autorange, 50/60Hz, True RMS, Crest Factor < 3.0)

Range
  • 0.200 ~ 1.000mA
  • 1.00 ~ 10.00mA
  • 10.0 ~ 100.0mA
  • 100 ~ 1000mA

Resolution
  • 0.001mA
  • 0.01mA
  • 0.1mA
  • 1mA

Ground / Leakage Current (50/60Hz, True RMS, Crest Factor < 3.0)
Range
  • 0.20 ~ 35.00A

Resolution
  • 0.01A

Accuracy of reading1
  • 2.0% ±0.03A
No user reviews available.