Home » MTP 5637 Clamp-On Ground Resistance Tester
MTP 5637 Clamp-On Ground Resistance Tester
Part Number:
MTP 5637
In Stock?
Stock may be available
please call (877)766-5412 to confirm
please call (877)766-5412 to confirm
Quantity
Price:
$1571.43
USD (change)




The MTP 5637 advances the usability of clamp-on ground testing.
The larger jaw opening allows tests on a wider variety of ground rods and installations. Auto-Detects if jaw is open or if there is ground noise.
Comes complete in hard sided carry case and calibration loop is included.
Othe features include:
The larger jaw opening allows tests on a wider variety of ground rods and installations. Auto-Detects if jaw is open or if there is ground noise.
Comes complete in hard sided carry case and calibration loop is included.
Othe features include:
- Non-Contact Ground Resistance Measurement
- No Auxiliary Electrode Needed
- Jaw Diameter 35 mm
- Jaw Opening 38 mm
- Range 0.025 – 1500 Ohm
- 116 Sets of Memory
- Programmable Hi and Lo Alarm
- Programmable Data Logging
- CAT II 600V, CAT III 300V, EN 61010-2-032
The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
Applications:
- Measure electrical ground rod and grid resistance
- Use on multi-grounded systems without disconnecting the ground rod under test
- Measure resistance and continuity of grounding loops around pads and buildings
- Measure leakage current flowing to ground or circulating in ground systems
- Conduct field surveys and retrieve and analyze readings at a later time
- Use on cell towers and telecommunication sites
- Use on pools, spas and other consumer installations
- Non-Contact Ground Resistance Measurement
- No Auxiliary Electrode Needed
- 0.025 - 1500 Ohms measurement range
- Ground Wire O 23mm/0.9 inch¯
- Leakage Current (0.200mA - 10.00mA)
- Hi-Lo Alarm (Go - No Go)
- Memory of 116 records
- Programmable Data Logging
- Auto Detect of Jaw Open and Ground Noise
- Compliant with Safety Standard EN61010-2
- CAT II 600V , CAT III 300V
General Specifications:
Jaw Opening: 38mm (1.49 inch¯)
Power Source: 9V Battery
Power Consumption: 40mA
Operating Temperature: 0°C to 40°C
Operating Humidity: Less than 80% RH
Dimensions: 258mm(L) x 100mm(W) x 47mm(H)
10.2¯(L) x 4¯(W) x 1.9¯(H)
Weight: 640g (1.4lbs)
Electrical Specifications:
Ground Resistance (Autorange):
Range
Resolution
Accuracy of reading1
1 Loop resistance noninductive, external field < 50A/m, external electrical field < 1V/m, conductor centered.
2 Resistance Measurement Frequency: 1.667KHz
Continuity
Beep if resistance < 40.00Ohm (Approximately)
Ground / Leakage Current (Autorange, 50/60Hz, True RMS, Crest Factor < 3.0)
Range
Resolution
Ground / Leakage Current (50/60Hz, True RMS, Crest Factor < 3.0)
Range
Resolution
Accuracy of reading1
Jaw Opening: 38mm (1.49 inch¯)
Power Source: 9V Battery
Power Consumption: 40mA
Operating Temperature: 0°C to 40°C
Operating Humidity: Less than 80% RH
Dimensions: 258mm(L) x 100mm(W) x 47mm(H)
10.2¯(L) x 4¯(W) x 1.9¯(H)
Weight: 640g (1.4lbs)
Electrical Specifications:
Ground Resistance (Autorange):
Range
- 0.025 ~ 0.250 Ohm
- 0.250 ~ 9.999 Ohm
- 10.00 ~ 99.99 Ohm
- 100.0 ~ 199.9 Ohm
- 200.0 ~ 400.0 Ohm
- 400.0 ~ 600.0 Ohm
- 600.0 ~ 1500.0 Ohm
Resolution
- 0.002 Ohm
- 0.02 Ohm
- 0.04 Ohm
- 0.4 Ohm
- 2 Ohm
- 5 Ohm
- 20 Ohm
Accuracy of reading1
- 1.5% 0.05 Ohm
- 1.5% 0.1 Ohm
- 2.0% 0.3 Ohm
- 3.0% 1.0 Ohm
- 5.0%5 Ohm
- 10% 10 Ohm
- 20% (Approx.)
1 Loop resistance noninductive, external field < 50A/m, external electrical field < 1V/m, conductor centered.
2 Resistance Measurement Frequency: 1.667KHz
Continuity
Beep if resistance < 40.00Ohm (Approximately)
Ground / Leakage Current (Autorange, 50/60Hz, True RMS, Crest Factor < 3.0)
Range
- 0.200 ~ 1.000mA
- 1.00 ~ 10.00mA
- 10.0 ~ 100.0mA
- 100 ~ 1000mA
Resolution
- 0.001mA
- 0.01mA
- 0.1mA
- 1mA
Ground / Leakage Current (50/60Hz, True RMS, Crest Factor < 3.0)
Range
- 0.20 ~ 35.00A
Resolution
- 0.01A
Accuracy of reading1
- 2.0% ±0.03A
Product brochures