Capable 3- and 4-point ground resistance tester with soil resistivity and stakeless clamp testing functions
The new Fluke 1623 GEO Earth Ground Tester offers an innovative solution, called Stakeless testing, to make your earth ground loop resistance testing quicker and easier. No need for a separate earth ground clamp.
The Fluke 1623 earth
ground tester is able to measure
earth ground loop resistances using
only clamps. With this test method,
two clamps are placed around the
earth ground rod and each are connected to the tester. No earth ground
stakes are used at all. A known, fixed
voltage is induced by one clamp and
the current is measured using the
second clamp. Then the tester automatically determines the resistance
of the earth ground rod.
This test method only works if a
bonded earth ground system exists for
the building or structure under test, but
most are. If there is only one path to
ground, like at many residential applications, the Stakeless method will not
provide an acceptable value and the Fall
of Potential test method must be used.
With Stakeless testing, the earth
ground rod does not need to be disconnected-leaving the bonded earth
ground system intact during test. Gone
are the days of spending time placing
and connecting stakes for each earth
ground rod on your system-a major
time saver. You can also perform earth
ground tests in places you've not
considered before: inside buildings,
power pylons, or anywhere you don't
have access to soil.
| RA 3-pole ground resistance measurement (IEC 1557-5) | ||
| Fluke 1623 | Fluke 1625 | |
| Measuring Voltage | Vm = 48 V ac | Vm = 20/48 V ac |
| Short circuit current | > 50 mA | 250 mA ac |
| Measure frequency | 128 Hz | 94, 105, 111, 128Hz |
| Resolution | 0.001 Ω to 10 Ω | 0.001 Ω to 100 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ | 0.001 Ω to 299.9 kΩ |
| Intrinsic error | ± (2 % of reading + 3 digit) | ± (2 % of reading + 2 d) |
| Operating error | ± (5 % of reading + 3 d) | ± (2 % of reading + 2 d) |
| RA 4-pole ground resistance measurement (IEC 1557-5) | ||
| Measuring Voltage | Vm = 48 V ac | Vm = 20/48 V ac |
| Short circuit current | > 50 mA | 250 mA ac |
| Measure frequency | 128 Hz | 94, 105, 111, 128Hz |
| Resolution | 0.001 Ω to 10 Ω | 0.001 Ω to 100 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ | 0.001 Ω to 299.9 kΩ |
| Intrinsic error | ± (2 % of reading + 3 d) | ± (2 % of reading + 2 d) |
| Operating error | ± (5 % of reading + 3 d) | ± (5 % of reading + 5 d) |
| RA 4-pole selective ground resistance measurement with current clamp | ||
| Measuring Voltage | Vm = 48 V ac | Vm = 20/48 V ac |
| Short circuit current | > 50 mA | 250 mA ac |
| Measure frequency | 128 Hz | 94, 105, 111, 128Hz |
| Resolution | 0.001 Ω to 10 Ω | 0.001 Ω to 100 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ | 0.001 Ω to 299.9 kΩ |
| Intrinsic error | ± (7 % of reading + 3 d) | ± (7 % Of reading + 2 d) |
| Operating error | ± (10 % of reading + 5 d) | ± (10 % of reading + 5 d) |
| Stakeless ground loop measurement | ||
| Measuring Voltage | Vm = 48 V ac | Vm = 20/48 V ac |
| Measure frequency | 128 Hz (125 Hz on request) | 94, 105, 111, 128Hz |
| Noise current (Iext) | Max. Iext = 10 A (ac) (RA < 20 O) Max. Iext = 2 A (ac) (RA < 20 O) | Max. Iext = 3 A |
| Resolution | 0.001 Ω to 0.1 Ω | 0.001 Ω to 10 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ | 0.001 Ω to 299.9 kΩ |
| Intrinsic error | ± (7 % of reading + 3 d) | ± (7 % Of reading + 2 d) |
| Operating error | ± (10 % of reading + 5 d) | ± (10 % of reading + 5 d) |
| Environmental Specifications | ||
| Working temperature | -10 °C to +50 °C | |
| Operating Temperature | 0 °C to +35 °C | |
| Storage Temperature | -20 °C to +60 °C | -30 °C to +60 °C |
| Climatic class | C1 (IEC 654-1), -5 °C to + 45 °C, 5 % to 95 % RH | |
| Protection type | IP56 for case, IP40 for battery door according to EN 60529 | |
| Safety Specifications | ||
| Safety Rating | CAT II, 300 V | |
| Mechanical & General Specifications | ||
| Display | 1999 digit LCD – display with special symbols, digit height 25 mm, fluorescent backlight | 2999 Digit LCD – 7 segment liquid crystal display with special symbols and backlight |
| Size | 133 mm x 187 mm x 250 mm | |
| Weight | Fluke 1623 + Fluke 1625 1.1 kg (including batteries) | |
| Warranty | Two years | |
| Battery Life | Typical > 3000 measurements | Typical 3000 measurements (RE+RH = 1 kΩ) Typical 6000 measurements (RE+RH = 10 kΩ) |